Introduction
Photovoltaic (PV) grid inverter is the core equipment in the PV grid power station, whose reliability; efficiency and security affect the whole PV system, and has a direct bearing on power capacity of the power station and operation.
Solar PV grid power system is composed of PV Modules, Grid inverter, Metering device and Distribution system. PV Module transforms Solar energy into DC power, and Grid inverter transforms DC power into sine wave current with same frequency and same phase of electricity grid and puts it into electricity grid.
Solar PV grid power system is the trend of solar PV power development, which stands for the most attractive energy utilization technology in 21 century. It puts energy directly into electricity grid, without storing energy by battery, make full use of electric power from renewable energy, decreasing the energy loss and reducing the system cost. Solar PV grid power system uses both Mains power and renewable energy as power supply for AC load, which reduces the load power shortage rate of the whole systems, meanwhile, the renewable energy grid system is used for peak modulation against public electricity grid.
Features & Benefits
Home appliance Small-sized PV station, Could be used in series
l Single MPPT (with 3 groups, with flexible configuration and installation)
l Outdoor waterproof design (IP65)
l Wide range of operating temperature: -25℃-+60℃,and in 50℃, it can keep the max power output
l Multi-lingual LCD display which could be set at user’s willing
l Islanding protection
l Inline waterproof block
l RS485 and USB communication port
l TUV CE certificate, comply with Germany VDE 0126-1-1 standard.
l Italy DK5940 certificate, Australia AS4777 certificate, CQC (including SUN certificate)
Technicial Specifications
| Model | EA3KLPV | EA5KLPV |
| Input (DC) | ||
| Max DC power | 3850Wp | 5500Wp |
| Max DC voltage | 520V | 520V |
| Start Voltage | 150V | 150V |
| Nominal DC voltage | 360V | 360V |
| Max DC current | 20A | 20A |
| Full-load MPP voltage range | 200~420V | 260~420V |
| Number of MPP-Trackers | 1 | 2 |
| MPPT efficiency (static) | >99% | >99% |
| Max input current | 19A | 20A |
| Insulation voltage | Basic insulation 3000Vdc / 1 min | Basic insulation 3000Vdc / 1 min |
| output (AC) | ||
| Nominal AC power | 3500W | 5000W |
| Nominal AC voltage | 230Vac | 230Vac |
| AC voltage range | 180Vac~260Vac | 180Vac~260Vac |
| Nominal AC current | 15A | 22A |
| Nominal frequency | 50Hz/60Hz | 50Hz/60Hz |
| Frequency tolerance range | 47~51.5Hz / 57~61.5Hz | 47~51.5Hz / 57~61.5Hz |
| Distortion (THD%) | <3% (at norminal power) | |
| DC current component | <75mA | <110mA |
| Power factor (cos phi) | >0.99 | >0.99 |
| Insulation voltage | Basic insulation 3000Vdc / 1 min | |
| Number of grid phases | 1 | 1 |
| Efficiency | ||
| Max efficency | 97.3% | 97.3% |
| Euro efficiency | 96.2% | 96.5% |
| General requirements | ||
| Standby consumption | 12W | 12W |
| Night consumption | 0W | 0W |
| Topology | transformerless | transformerless |
| Mean Time Between Failure (MTBF) | 40,000h | 40,000h |
| Standard warranty | 20 years | 20 years |
| Protection | ||
| Reverse protection (Input) | Yes | Yes |
| Short-circuit protection (Input/Output) | Yes | Yes |
| Overload protection (Output) | Yes | Yes |
| Undervoltage / Overvoltage protection point (Grid) | 160Vac/276Vac | 160Vac/276Vac |
| Undervoltage / Overvoltage protection point (DC) | 120V/550V | 120V/550V |
| Underfrequency / Overfrequency protection point (Grid) | 52Hz/ 46.5Hz ; 62Hz/ 56.5Hz | |
| Leakage current protection | DIN VDE 0126-1-1 | |
| Fault current protection | ||
| Anti-islanding protection | ||
| Standards & guidelines | ||
| Certificates | TUV ,CE , DIN VDE0126-1-1,comply with the DK5940 | |
| EMC | EN61000-6-1,EN61000-1-2,EN61000-6-3 , EN61000-1-4 / Class B | |
| Safety and regulatory | IEC 62109-1 | |
| Other | ||
| Dimensions(L×H×W) | 390 mm ×480 mm ×200mm | |
| Weight | 25kg | 30kg |
| Acoustic Noise level | 50dB(A) | 50dB(A) |
| Operation temperature range | -20℃~+60℃ (>45℃ derating) | |
| Relative humidity | 0~90 % | 0~90 % |
| Protection type compliant with EN 60529 | IP65 | IP65 |